Configuration — HID Aero Access Control System
Everything you can add with this adapter: where it goes in the tree, what you fill in, and what
you can tell it to do.
HID Aero X1100 Controller
Intelligent controller with integrated I/O
|
|
| Add it under |
nothing — this is the top of the tree |
| Identified by |
nothing — there is only one |
| Role |
— |
What you fill in
| Setting |
Required |
Default |
Accepted values |
What it does |
| connection_mode |
yes |
Server |
ConnectionMode |
Server = adapter connects to panel, Client = panel connects to adapter |
| tls_mode |
yes |
Optional |
TlsMode |
TLS encryption mode for communication |
| serial_number |
optional |
— |
text |
Panel serial number for verification (optional, logged on mismatch) |
| ip_address |
optional |
— |
host name or IP address |
Controller host or IP address |
| port |
optional |
3001 |
1–65535 |
TCP communication port |
| password |
optional |
— |
text |
Logon password (stored as a secret) |
| rs485_master_key |
optional |
— |
text |
AES master key for RS-485 encryption (32 hex chars = 128-bit) (stored as a secret) |
| rs485_port1_baud_rate |
yes |
Baud115200 |
Rs485BaudRate |
Speed of the RS-485 line that carries port 1 modules; every module on that line must be set to the same speed |
| rs485_port2_baud_rate |
yes |
Baud115200 |
Rs485BaudRate |
Speed of the RS-485 line that carries port 2 modules; every module on that line must be set to the same speed |
What you can command it to do
| Command |
What happens |
| Reset |
Reset to initial state |
HID Aero X100 Reader Interface
RS-485 reader interface module with 2 reader ports
|
|
| Add it under |
HID Aero X1100 Controller (up to 32) |
| Identified by |
the bus + address (address space sio_module) you fill in below |
| Role |
— |
What you fill in
| Setting |
Required |
Default |
Accepted values |
What it does |
| bus |
yes |
— |
SioBus |
RS-485 bus (Port1 or Port2) |
| address |
yes |
— |
0–15 |
Hardware address on bus (0-15) |
| encryption_enabled |
optional |
false |
yes / no |
Enable RS-485 AES encryption for this module |
RS-485 input expansion module with 19 monitor points
|
|
| Add it under |
HID Aero X1100 Controller (up to 32) |
| Identified by |
the bus + address (address space sio_module) you fill in below |
| Role |
— |
What you fill in
| Setting |
Required |
Default |
Accepted values |
What it does |
| bus |
yes |
— |
SioBus |
RS-485 bus (Port1 or Port2) |
| address |
yes |
— |
0–15 |
Hardware address on bus (0-15) |
| encryption_enabled |
optional |
false |
yes / no |
Enable RS-485 AES encryption for this module |
HID Aero X300 Output Module
RS-485 output expansion module with 12 relay outputs
|
|
| Add it under |
HID Aero X1100 Controller (up to 32) |
| Identified by |
the bus + address (address space sio_module) you fill in below |
| Role |
— |
What you fill in
| Setting |
Required |
Default |
Accepted values |
What it does |
| bus |
yes |
— |
SioBus |
RS-485 bus (Port1 or Port2) |
| address |
yes |
— |
0–15 |
Hardware address on bus (0-15) |
| encryption_enabled |
optional |
false |
yes / no |
Enable RS-485 AES encryption for this module |
Reader Port
Physical reader connection point
|
|
| Add it under |
HID Aero X1100 Controller (up to 4), HID Aero X100 Reader Interface (up to 2) |
| Identified by |
nothing — there is only one |
| Role |
counts towards anti-passback |
What you fill in
| Setting |
Required |
Default |
Accepted values |
What it does |
| address |
yes |
— |
a number |
Reader number on SIO (0-based) |
| interface_type |
yes |
Wiegand |
ReaderInterfaceType |
Reader interface type |
| osdp_address |
optional |
— |
0–3 |
OSDP device address (when using OSDP) |
| osdp_baud_rate |
optional |
Baud9600 |
OsdpBaudRate |
OSDP baud rate |
| osdp_secure_channel |
optional |
false |
yes / no |
Enable OSDP secure channel |
| trim_zero_bits |
optional |
false |
yes / no |
Trim zero bits at beginning and end of card data (dt_fmt ZTRIM) |
| format_to_nibble_array |
optional |
false |
yes / no |
Mag stripe Track 2 nibble array decode (dt_fmt T2FMT) |
| allow_bidirectional_mag_decode |
optional |
false |
yes / no |
Allow bi-directional mag stripe decode (dt_fmt BIDIR) |
| keypad_mode |
optional |
None |
KeypadMode |
Keypad data format |
| osdp_disable_auto_discovery |
optional |
false |
yes / no |
Disable OSDP auto discovery to prevent address conflicts |
| osdp_diagnostic_tracing |
optional |
false |
yes / no |
Enable OSDP diagnostic tracing for debugging |
What you can command it to do
| Command |
What happens |
| Enroll Card |
Start card enrollment process on reader |
Monitor Point
Physical input point (sensor, contact, REX)
|
|
| Add it under |
HID Aero X1100 Controller (up to 7), HID Aero X100 Reader Interface (up to 7), HID Aero X200 Input Module (up to 19), HID Aero X300 Output Module (up to 5) |
| Identified by |
nothing — there is only one |
| Role |
— |
What you fill in
| Setting |
Required |
Default |
Accepted values |
What it does |
| address |
yes |
— |
a number |
Input number on SIO (0-based) |
| supervision |
yes |
NormallyOpenNoEol |
InputSupervision |
Input supervision type |
| debounce |
optional |
4 |
0–15 |
Debounce scan multiplier (0-15) |
| hold_time |
optional |
5 |
2–15 |
Motion detector hold time in seconds |
| mode |
optional |
Normal |
MonitorPointMode |
Monitor point mode (normal/non-latching/latching) |
| entry_delay |
optional |
0 |
0–65535 |
Entry delay in seconds (0 = none) |
| exit_delay |
optional |
0 |
0–65535 |
Exit delay in seconds (0 = none) |
| log_mode |
optional |
LogAll |
MonitorPointLogMode |
Event logging filter mode |
Control Point
Physical output point (relay)
|
|
| Add it under |
HID Aero X1100 Controller (up to 4), HID Aero X100 Reader Interface (up to 4), HID Aero X200 Input Module (up to 2), HID Aero X300 Output Module (up to 12) |
| Identified by |
nothing — there is only one |
| Role |
— |
What you fill in
| Setting |
Required |
Default |
Accepted values |
What it does |
| address |
yes |
— |
a number |
Output number on SIO (0-based) |
| default_pulse_time |
optional |
2 |
1–255 |
Default pulse duration in seconds |
What you can command it to do
| Command |
What happens |
| Activate |
Activate output relay or control point |
| Deactivate |
Deactivate output relay or control point |
| Push |
Momentary activation (button press) |
Door
Access point with entry reader and optional exit reader for anti-passback
|
|
| Add it under |
HID Aero X1100 Controller (up to 32), HID Aero X100 Reader Interface (up to 4) |
| Identified by |
nothing — there is only one |
| Role |
an access point people pass through |
What it must be linked to
| Setting |
Link to |
Required |
What it is for |
| entry_reader |
Reader Port |
yes |
Entry side reader port |
| exit_reader |
Reader Port |
optional |
Exit side reader port (for anti-passback) |
| strike |
Control Point |
optional |
Strike relay for door lock |
| door_contact |
Monitor Point |
optional |
Door contact sensor |
| rex |
Monitor Point |
optional |
Request to exit button |
What you fill in
| Setting |
Required |
Default |
Accepted values |
What it does |
| strike_time_min |
optional |
1 |
1–60 |
Minimum strike time in seconds |
| strike_time_max |
optional |
30 |
1–255 |
Maximum strike time in seconds |
| strike_mode |
optional |
DeactivateOnOpen |
StrikeMode |
Strike control mode |
| held_open_time |
optional |
30 |
1–32767 |
Held open alarm delay (2-second units) |
| credential_mode |
optional |
CardOnly |
CredentialMode |
Access credential mode |
| extended_feature |
optional |
None |
AcrExtendedFeature |
Extended ACR feature type |
What you can command it to do
| Command |
What happens |
| Open |
Open door momentarily (unsecure strike temporarily) |
| Lock |
Lock door - deny entry, cards included, until unlocked |
| Unlock |
Unlock door - return to normal operation, cards decide |
Monitor Point Group
Alarm zone grouping inputs and door alarms for arm/disarm
|
|
| Add it under |
HID Aero X1100 Controller (up to 128) |
| Identified by |
nothing — there is only one |
| Role |
— |
What you fill in
| Setting |
Required |
Default |
Accepted values |
What it does |
| address |
yes |
— |
0–127 |
Monitor point group number (0-127) |
What you can command it to do
| Command |
What happens |
| Arm |
Arm security monitoring |
| Force Arm |
Force arm partition, bypassing open zones |
| Disarm |
Disarm security monitoring |
Monitor point assigned to an alarm zone
|
|
| Add it under |
Monitor Point Group (up to 128) |
| Identified by |
nothing — there is only one |
| Role |
— |
What it must be linked to
| Setting |
Link to |
Required |
What it is for |
| monitor_point |
Monitor Point |
yes |
Physical input to monitor |
What you fill in
| Setting |
Required |
Default |
Accepted values |
What it does |
| address |
yes |
— |
0–127 |
Index within the group |
What you can command it to do
| Command |
What happens |
| Bypass |
Temporarily exclude from monitoring |
| Cancel Bypass |
Cancel bypass and resume monitoring |
Door Alarm
Door forced/held open alarm assigned to an alarm zone
|
|
| Add it under |
Monitor Point Group (up to 128) |
| Identified by |
nothing — there is only one |
| Role |
— |
What it must be linked to
| Setting |
Link to |
Required |
What it is for |
| target_door |
Door |
yes |
Door to monitor for forced/held open alarms |
What you fill in
| Setting |
Required |
Default |
Accepted values |
What it does |
| address |
yes |
— |
0–127 |
Index within the group |
| alarm_type |
optional |
Both |
DoorAlarmType |
Which door alarm conditions to monitor |
What you can command it to do
| Command |
What happens |
| Bypass |
Temporarily exclude from monitoring |
| Cancel Bypass |
Cancel bypass and resume monitoring |