What it can do — HID Aero Access Control System
Feature by feature, as assessed on 2026-07-24. Read the limitation column before you
promise a customer something the hardware cannot do.
Connection, health and audit
| Feature |
Supported |
Limitation |
| Connection & session |
Partially |
The system has to reach the panel at a known address, so a panel that dials in by itself cannot be used, and the encrypted link cannot be checked against a certificate. |
| Liveness / keepalive |
Yes |
— |
| Time synchronization |
Yes |
— |
| Offline audit recovery |
Partially |
Events recorded while the connection was down are sent by the panel afterwards, but there is no guarantee how far back they reach or that none of them arrives twice. |
| Health & supervision |
Yes |
— |
| Configuration & reset audit |
Partially |
Changes made to the panel settings are recorded, but wiping the panel back to its factory or default state is not recorded as its own audit entry. |
| Configuration discovery |
Partially |
The panel, its expansion modules, inputs, outputs, readers and doors all have to be entered by hand; nothing is read in from the hardware automatically. |
Access control
| Feature |
Supported |
Limitation |
| Credential management |
Partially |
People can be given cards and PIN codes, but fingerprints, phone credentials and cards that stop working after a set number of uses cannot be sent to the panel. |
| Card formats |
Partially |
Cards are recognised only by their full number in one of seven fixed lengths, so the site and card numbers printed on a card cannot be entered separately. |
| Sync mode |
Yes |
— |
| Reset & restore |
Yes |
— |
| Double-sync safety |
Partially |
Sending the same people to the panel a second time is expected to change nothing, but this has not been confirmed on real hardware. |
| Schedules / time profiles |
Yes |
— |
| Access levels / groups |
Yes |
— |
| Holidays |
Yes |
— |
| Antipassback |
Yes |
— |
| Door control |
Partially |
A door can be released for a moment and switched between locked and unlocked, but it cannot be held open permanently and there is no single emergency lockdown. |
| Reader mode / enable |
Partially |
A reader keeps the mode it was given when it was set up; it cannot be switched off or moved to another mode, such as card plus PIN, while the system runs. |
| Access events |
Yes |
— |
| Enrollment |
Partially |
A new card can be registered by presenting it at a reader within a minute, but PIN codes, fingerprints and face data still have to be entered by hand. |
Intrusion detection
| Feature |
Supported |
Limitation |
| Arm / disarm |
Partially |
An area can be armed fully, armed despite open detectors, and disarmed, but partial modes such as guarding only the perimeter while people stay inside are not available. |
| Bypass |
Yes |
— |
| Alarm reset |
No — the hardware cannot do it |
A triggered alarm cannot be cleared from the system; someone has to reset it at the panel or a keypad. |
| Partitions / zones |
Yes |
— |
| Alarms / tampers / troubles / restores |
Yes |
— |
| User-code management |
Partially |
PIN codes reach the panel, but a code that may only arm, or one that silently signals a person is being forced, cannot be set up from the system. |
| Entry / exit delay |
Partially |
Each detection point has its own entry and exit delay time, but the running countdown after someone enters or before an area arms is not shown anywhere. |
| Sounder / alarm control |
No — the hardware cannot do it |
Sirens cannot be silenced, sounded or tested from the system; that has to be done at the panel. |
Safety
| Feature |
Supported |
Limitation |
| Panic / duress / emergency |
Partially |
It is reported when someone enters the code that signals being forced, but panic, medical and evacuation calls are not, and no emergency can be raised from the system. |
| Feature |
Supported |
Limitation |
| Inputs |
Yes |
— |
| Outputs |
Yes |
— |
| Output schedules |
No — the hardware cannot do it |
Outputs and relays can only be switched on and off as they are needed; they cannot be given a timetable that the panel follows on its own. |
Manufacturer gateway
| Feature |
Supported |
Limitation |
| External lifecycle |
Yes |
— |
| Shared transport |
Yes |
— |
| Platform limits / SDK errors |
Partially |
Commands that fail, time out or are refused by the panel are retried and reported, but a dial-in connection and certificate-checked encryption cannot be selected at all. |