Configuration — LITES MHU116/117

Everything you can add with this adapter: where it goes in the tree, what you fill in, and what you can tell it to do.

MHU Fire Panel

LITES MHU116/117 master (ustredna). Connection root; one per accessed panel that holds full data of all masters.

Add it under nothing — this is the top of the tree
Identified by nothing — there is only one
Role —

What you fill in

Setting Required Default Accepted values What it does
ip_address yes — host name or IP address IP address of Modul periferii 2 (DPE-2 / MPE-2) Ethernet interface
port yes — 1–65535 DPE-2 TCP port from the configuration program; not Modbus 502
address yes — 1–16 Master number as shown on the panel display (1 to 16)

What you can command it to do

Command What happens
Reset Reset to initial state
Mute Buzzer Silence buzzer alarm
Mute Sounder Silence siren alarm
Reactivate Sounder Re-enable previously muted sounder
Activate Activate alarm or function

MHU Network Master

Another master (tablo MHS 817 or networked MHU 116/117) reached through the connected panel. Owns its own panel-level history events; commands go through the connected panel.

Add it under MHU Fire Panel
Identified by the address you fill in below
Role —

What you fill in

Setting Required Default Accepted values What it does
address yes — 1–16 Master number as shown on the panel display (1 to 16)

Fire Group

Fire group (pozarni skupina). 116/117 groups 1..304.

Add it under MHU Fire Panel
Identified by the address you fill in below
Role —

What you fill in

Setting Required Default Accepted values What it does
address yes — 0–65535 System address (SysAdr) from the configuration program. Groups 1–304 use SysAdr 0–303. A group on another master uses that master's address block.

What you can command it to do

Command What happens
Bypass Temporarily exclude from monitoring
Cancel Bypass Cancel bypass and resume monitoring
Test Enter test mode
Finish Test Exit test mode

Fire Detector

Addressable fire detector or point on a loop/module.

Add it under MHU Fire Panel
Identified by the address you fill in below
Role —

What you fill in

Setting Required Default Accepted values What it does
address yes — 0–65535 System address (SysAdr) from the configuration program, for example 768 for the first detector on user module 1. A point on another master uses that master's address block.

What you can command it to do

Command What happens
Bypass Temporarily exclude from monitoring
Cancel Bypass Cancel bypass and resume monitoring
Test Enter test mode
Finish Test Exit test mode

Fire Input

Input contact whose active state maps to a PQ state via message_level.

Add it under MHU Fire Panel
Identified by the address you fill in below
Role —

What you fill in

Setting Required Default Accepted values What it does
address yes — 0–65535 System address (SysAdr) from the configuration program. A point on another master uses that master's address block.
message_level optional Alarm InputMessageLevel How an input activation is shown (Alarm, Warning, Information, Silent).

What you can command it to do

Command What happens
Bypass Temporarily exclude from monitoring
Cancel Bypass Cancel bypass and resume monitoring
Test Enter test mode
Finish Test Exit test mode

Fire Output

Panel output (siren / relay / open collector).

Add it under MHU Fire Panel
Identified by the address you fill in below
Role —

What you fill in

Setting Required Default Accepted values What it does
address yes — 0–65535 System address (SysAdr) from the configuration program. A point on another master uses that master's address block.

What you can command it to do

Command What happens
Activate Activate output relay or control point
Deactivate Deactivate output relay or control point
Bypass Temporarily exclude from monitoring
Cancel Bypass Cancel bypass and resume monitoring
Test Enter test mode
Finish Test Exit test mode