What it can do — LITES MHU116/117

Feature by feature, as assessed on 2026-09-21. Read the limitation column before you promise a customer something the hardware cannot do.

Connection, health and audit

Feature Supported Limitation
Connection & session Yes —
Liveness / keepalive Yes —
Time synchronization Yes —
Offline audit recovery Partially Events from a short disconnect come back in order. After a very long outage some events may not come back; that case is not yet proven.
Health & supervision Yes —
Configuration & reset audit Yes —
Configuration discovery Yes —

Fire detection

Feature Supported Limitation
Fire panel state Partially Day and night are shown as the panel sets them; Protequ cannot switch the mode. The pre-alarm, conditional alarm and technological alarm indications on the panel tile have not yet been confirmed on a real panel.
Fire detection & address state Yes —
Fire signaling outputs Partially Brigade routing and fire-service panels are not separate devices. Mute sounder silences the external acoustics; it does not enable or disable the siren circuit.
Fire intervention window Partially Confirmation and investigation windows are shown when the panel starts them. Protequ cannot change their length, and the remaining-time figure has not been confirmed against the panel clock.
Fire system control Partially Reset, mute buzzer, mute and reactivate sounders, manual alarm, bypass, test and output Activate work. Enabling or disabling the siren circuit and changing delays are not offered. Day and night cannot be commanded.

Inputs and outputs

Feature Supported Limitation
Inputs Partially Protequ cannot close an input. The contact is read only; the operator can bypass it or put it in test. End-of-line supervision is not configured from Protequ.
Outputs Partially Outputs can be activated, deactivated and bypassed. A timed or pulsed activation cannot be commanded from Protequ.
Output schedules No — the hardware cannot do it Output timing and schedules cannot be programmed from Protequ.