What it can do — Schrack Integral ISP-IP

Feature by feature, as assessed on 2026-09-21. Read the limitation column before you promise a customer something the hardware cannot do.

Connection, health and audit

Feature Supported Limitation
Connection & session Yes —
Liveness / keepalive Yes —
Time synchronization Yes —
Offline audit recovery No — the hardware cannot do it Events that happen while the link is down are not replayed afterwards; Protequ only shows the current states once the panel is connected again.
Health & supervision Yes —
Configuration & reset audit No — the hardware cannot do it The panel does not report when its project is restored or wiped, so those actions leave no line in the Protequ audit.
Configuration discovery No — the hardware cannot do it The panel does not send its device tree. Groups and detectors appear in Protequ only after you import the Intmel XML export.

Fire detection

Feature Supported Limitation
Fire panel state Yes —
Fire detection & address state Partially Flooding zones, fire-brigade panels, alarm areas and printers are not modelled as their own devices; unusual states from them appear as a supervisory note on the panel.
Fire signaling outputs Partially Sounders can be muted and reactivated. HAL and SAL relays hold until the alarm is reset and are not treated as sirens.
Fire intervention window Yes —
Fire system control Partially Mute buzzer works only after a full fire alarm, not during T1 or T2. Battery check and simulate-alarm are deliberately not offered.

Inputs and outputs

Feature Supported Limitation
Inputs Partially Protequ cannot close an input. The contact is read only; the operator can bypass it or put it in test.
Outputs Partially Outputs can be switched on or off and inhibited. There is no separate general On/Off/Reset command beyond those.
Output schedules No — the hardware cannot do it Output timing and schedules are set in the Integral project; they cannot be programmed from Protequ.