Skip to content

FireControlOutput

Overview

Fire protection control output function for outputs driven by fire logic: suppression, evacuation, door release, HVAC shutdown, smoke control, or other fire-control relays.

  • Added in: PQ Framework 2.3
  • Namespace: Pq.Adapters.Framework

When to Use

  • Fire protection control outputs
  • Suppression control outputs
  • Smoke extraction, HVAC shutdown, evacuation relays
  • Panel addresses named "fire control" / pozarni ovladani

States

State Status id Description
On control.on Output on
Off control.off (hidden) Output off
OutputActive fire.output.active Fire-control output active
Disabled fire.disabled Fire-control output disabled

Off is the hidden default state: SetOff(ct) publishes no status string, so an idle output reports the function as cleared.

Actions

Action Target State Event
FireControlActivated(timestamp) OutputActive pq.event.fire.control.activated
FireControlDeactivated(timestamp) Off pq.event.fire.control.deactivated
FireControlEnabled(timestamp) Off pq.event.fire.control.enabled
FireControlDisabled(timestamp) Disabled pq.event.fire.control.disabled

YAML Example

device_types:
  - type_id: FireControlRelay
    name: "Fire Control Relay"
    functions:
      FireControlOutput:

See Also

  • Functions: Output - Generic output relay
  • Functions: FireRouting - Fire alarm transmission output