Sounder

Overview

Audible alarm signaling output for a siren, bell, or buzzer outside the fire-specific model.

When to Use

  • Intrusion alarm sirens and bells
  • Audible annunciators
  • Alarm buzzers with explicit activation events

Use SounderSupervision on the same Thing when the device reports circuit health.

States

State Status id Description
On control.on Sounder is active
Off control.off (hidden) Sounder is inactive

Off is the hidden default state: SetOff(ct) publishes no status string, so the function status is removed from the published status snapshot.

Actions

Action Target State Event
SounderActivated(timestamp) On pq.event.alarm.sounder.activated
SounderDeactivated(timestamp) Off pq.event.alarm.sounder.deactivated
SounderSilenced(timestamp) Off pq.event.alarm.sounder.silenced

Each action sets the target state and publishes its listed event. Route a confirmed device transition to the matching action; do not publish the same PqEvent separately.

YAML Example

device_types:
  - type_id: AlarmSiren
    functions:
      Sounder:
      SounderSupervision: